Products list News product in 2016

TCD-300

Author: admin Viewed: 219Close

2018-06-23 08:41:30

  • TCD-300
  • TCD-300
Product model: TCG-300 series
shape size: 72 (wide) *72 (high) *45mm
1. Summary:
TC series temperature control instrument can replace the traditional pullout type or potentiometer type digital display instrument, it can be set freely with light touch key, single row three bit LED display, simple PID control or two bit return difference control, and the error correction function, and the sensor error correction function, the instrument has reliable control performance, high performance price ratio and should be used. It has the advantages of wide range and so on.
Two. Technical parameters:
Input type and measurement range: -K (0~999 C) E (0~800 C) J (0~999 C) Pt100 (-199 ~ 600) Cu50 (-50 to 150 degrees C) NTC (-50 to 150 C)
Display accuracy: + 1%F. S + 1B. Additional cold junction compensation error is less than 2 C.
Control mode: two position control (adjustable backlash) or PID control.
Error setting range: 1~20 C
Sensor error translation correction range: -20 ~ 20 C
Output mode: relay normally open normally closed contact AC220V/5A; SSR trigger signal: drive current greater than 15mA voltage greater than 9V
Working power supply: AC85 to 242V 50Hz/60Hz power consumption: less than 3W or others according to customer requirements
Instrument working environment: 0~50 C, relative humidity less than 85%, no corrosive and no strong electromagnetic radiation occasions.
Three, product selection:

TC □—  □     □      □

1  2     3      4       5

1: the product series Temperature Controller
2: for outer size and opening size (unit: mm)
H: 160 x 80 x 45 opening 152 x 76 A: 96 * 96 * 45 aperture 92 * 92
B: 60 x 120 x 45 openings 56 * 116 D:72 x 72 * 45 openings 68 * 68
E: 48 x 96 x 45 opening 44 x 92 F: 96 * 48 * 45 aperture 92 * 44
G: 48 X 48 x 45 opening 44 x 44 S: 80 * 160 * 45 aperture 76 * 156
K:48 * 24 x 45 opening 152 x 76 C:80 x 120 x 35 (wall mounted)
FC:76 * 35 * 77 opening 70 x 29 L:76 * 35 * 45 standard DIN guide rail installation
3: operation display mode:
1: two key touch switch operation, three digit display.
2: two key touch switch settings, single row three digit display, two bit control.
3: two key touch switch settings, single row three digit display, two bit time proportional control.
4: two key touch switch settings, single row three digit display, two bit simple PID control
5: two key touch switch settings, single row three digit display, three bit backlash control heating
6: two key touch switch settings, single row three digit display, three position backlash control refrigeration
4: type of input signal:
1. thermocouple (K E J) 2. thermal resistance (PT100 CU50)
3. thermistors (NTC 25 C @10K B=4100 or 25 C @5K B=3900 or specific NTC)
4.4-20MA standard current signal, corresponding to 0~999 display
5: suffix R: relay output (220V current less than 5A) G: solid state relay control signal output ON when 5-30VDC, OFF 0V
D: high-power relay output (220V current less than 30A)
Support: 7277